ABSTRACT
Recently, the power quality sensitive loads such as computer and
communications are so increased that the power supply with good power
quality has come to the fore.However,it is possible that the public grid is
interrupted by unexpected fault.Therefore,the UPS(uninterruptible power
supply)has be come an alternative solution to solve this problem.Generally,
the UPS consist of a rectifier,a battery,and a PWM inverter and recently
they use IGBT PWM rectifier to reduce input THDi and improve the input
power factor.
In this configurations the three-phase four-wire inputUPS is widely
used to eliminate the transformers in the UPS system.The aims of control
algorithm for the IGBT PWM rectifierin three-phase four-wire UPS is a
unity power factor.The SVM(space vector modulation)is one of the most
popular and preferable PWM scheme because it reduces the commutation
losses and harmonics in the output voltage,and has higher modulation
index than SPWM(sinusoidal PWM)but they need a 3D SVM to control
three-phase four-wire PWM rectifier and have some difficulties like as
selection of inductance of input inductor and controls the neutral current.
To improve this problem the another control algorithm which controls
each phase individually has been suggested but this control algorithm use
analog based control is sensitive and unstable.So another new
algorithm which is added d-q control to control algorithm which controls
each phase individually is suggested and it can control stably and can
reduce neutral current too.This can be seen by computer simulation and
experimental result.